MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Car-top stop switch box missing knock-out hole cover, exposed electrical wires.
|
4/12/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Jack drain tube to be routed to a measurable container in pit, currently 1 jack drains straight to tank.
|
4/12/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
4/7/2023
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
4/12/2023
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
1200.6
|
|
|
The code data plate required by A17.1 2016, section 8.9, shall be provided in plain view, securely attached to each main line disconnect or controller.
|
4/12/2023
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
4/12/2023
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Non-elevator related items shall not be stored in machine room (shredder, paperwork, sorter).
|
4/12/2024
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag.
|
4/12/2024
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
MCP Fire service testing must be properly documented monthly on log sheet.
|
4/12/2024
|
conversion
|
conversion
|
n/a
|
|
|
Pit light shall work.
|
6/22/2018
|
conversion
|
conversion
|
n/a
|
|
|
Machine room shall not be used for storage of non-elevator related materials.
|
6/22/2018
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Up to date operating certificate is required in the machine room.
|
4/12/2023
|