Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Pit light shall work. 6/22/2018
conversion conversion n/a Machine room shall not be used for storage of non-elevator related materials. 6/22/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 4/7/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 4/12/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/12/2023
A17.1-1996 : Elevators 2.14 - Code data plate 1200.6 The code data plate required by A17.1 2016, section 8.9, shall be provided in plain view, securely attached to each main line disconnect or controller. 4/12/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up to date operating certificate is required in the machine room. 4/12/2023
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. 4/12/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 MCP Fire service testing must be properly documented monthly on log sheet. 4/12/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Non-elevator related items shall not be stored in machine room (shredder, paperwork, sorter). 4/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Jack drain tube to be routed to a measurable container in pit, currently 1 jack drains straight to tank. 4/12/2024
MO Minimum : Elevators (A) - Hoistways (A)16 Car-top stop switch box missing knock-out hole cover, exposed electrical wires. 4/12/2024