Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/12/2023
MO Minimum : Elevators (A) - Hoistways (A)16 No No Car-top stop switch box missing knock-out hole cover, exposed electrical wires. 4/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Jack drain tube to be routed to a measurable container in pit, currently 1 jack drains straight to tank. 4/12/2024
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. 4/12/2024
conversion conversion n/a No No Machine room shall not be used for storage of non-elevator related materials. 6/22/2018
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No MCP Fire service testing must be properly documented monthly on log sheet. 4/12/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) No No Non-elevator related items shall not be stored in machine room (shredder, paperwork, sorter). 4/12/2024
conversion conversion n/a No No Pit light shall work. 6/22/2018
A17.1-1996 : Elevators 2.14 - Code data plate 1200.6 No No The code data plate required by A17.1 2016, section 8.9, shall be provided in plain view, securely attached to each main line disconnect or controller. 4/12/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 4/7/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 4/12/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up to date operating certificate is required in the machine room. 4/12/2023