Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working. 8/16/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.1.7 x 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. 11/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 8/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.16 - Traveling cables and junction boxes 2.8.1 The traveling cables shall be installed using one of the approved methods required by NFPA 620.41. Note: The cable is hung on a EMT clamp which isn't allowed, and may cause damage to the cable over time. 8/21/2023