Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 8/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation x Provide an audible signal while in recall.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Main hoisting ropes undersized. Min.469 actual .460 4/9/2019
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x Emergency lights not working. 6/29/2021
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x Emergency alarm not working. 6/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x All landing doors need maintenance, and adjustments. Rollers, upthrusts, eccentrics, etc. 6/29/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices x x Supply test of fire alarm devices 6/29/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) x seal voids and penetrations in hoistway 6/29/2021