Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3a No No Access to machine space is dangerous. Need steps from gate to the ground outside. 9/17/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No All required maintenance records need to be supplied by Otis
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No BAD KEY SWITCH IN HALLWAY
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d No No Door to equipment room needs to be self closing and locking 9/17/2021
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 No No Extension cord run from somewhere else thru machine room needs to be removed and hole patched in wall 9/17/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3a No No MACHINE ROOM DOOR IS REQUIRED TO BE SELF LOCKING
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d No No machine room door not self closing or locking
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d No No Machine room door not self locking or closing
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No maintenance records
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No MUST HAVE A CURRENT TEST TAG
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 No No NEEDS IN CASE OF FIRE USE STAIRS SIGNS
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3a No No NEEDS STAIRS OFF OF LANDING TO ACCESS MECHINE ROOM. CURRENTLY A 5' JUMP DOWN
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No PHASE 1 FIRE SERVICE INSTRUCTIONS NOT LEGIBLE
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 210.13 No No Phase I operating instructions and key switch bezel need to be replaced, they are illegible 9/17/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No PHONE IS NOT WORKING
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No Pit light is out 9/17/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3a No No Very steep grass slope, dangers to travel, change access. Gate in handrail ?
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3a No No very steep slop to climb to get to machine room. Install different access