A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
x
|
Fire service hat lens on car operating panel has been knocked out and is missing.
|
8/19/2020
|
A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
|
|
Need to identify unmarked floor lockout keyswitch located on car operating panel.
|
8/26/2020
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Elevator machine room door needs to be self locking.
|
8/26/2020
|
A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
|
|
Need to identify floor lockout keyswitch on car operating panel to corresponding car call that it locks out.
|
8/26/2020
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Machine room door needs to be non-defeatable and self locking.
|
8/26/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No documentation of maintenance or testing in on site maintenance record log.
|
7/15/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(c)(5)
|
|
|
Written checkout procedure for overspeed valve not on site. Needs to be kept in machine room.
|
7/15/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Test and log firefighter operation monthly
|
7/15/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Replace missing hoistway door unlocking rollers on first and second floor.
|
3/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
Door unlocking rollers are missing on 1st and 2nd floor hoistway doors.
|
8/19/2020
|