Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 2/24/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 2/24/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No The steel in the pit and the hydraulic lines in the pit are extremely rusted. Monitor condition and take corrective action as needed. 2/24/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. 5/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No The steel and hydraulic lines in the pit are extremely rusted. Monitor and correct as needed. 2/24/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No Pit steel and hydraulic lines in pit are extremely rusted. Examine condition and take corrective action as needed. 2/24/2026
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean and dry. 2/24/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up to date operating certificate required in machine room. 2/24/2026