A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
The in car emergency lighting shall be operational.
|
8/20/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The alarm bell shall be operational on main and auxiliary power.
|
8/20/2020
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
5/6/2021
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
The cab lighting shall be guarded. The light bulls need to be protected to contain any broken glass in the event of breakage.
|
5/6/2021
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
6/22/2022
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
100.3d
|
|
|
A permanent and unobstructed means of access shall be provided to machine room. Machine room door is blocked by racks of chairs and other miscellaneous equipment.
|
5/13/2025
|