Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/21/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/28/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/11/2021
conversion conversion n/a Replace the hydraulic cylinder parking to stop oil from leaking. 12/6/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The car top lighting shall be operational. 6/11/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in-car telephone shall be operational. The phone intermittently does not work, and when it does, the audio is broken up and cannot be understood. 3/25/2024
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit lighting shall be operational. 6/11/2021
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Remove the oil from the pit. 6/11/2021