A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
Yes
|
No
|
Standby emergency power needs to be tested. Re-inspection required
|
5/6/2022
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Testing of emergency generator operation needs to be performed
|
5/17/2024
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Oil recovery bucket is full. Determine if packing is leaking.
|
12/29/2025
|
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
1004.2(b)(19)
|
No
|
No
|
The hydraulic jack packing is leaking excessively and shall be replaced.
|
12/29/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Testing of emergency generator power operation needs to be scheduled, tested & witnessed by an inspector to complete this inspection. Re-inspection required
|
8/21/2026
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Two way communication could not be established, needs repaired. Re-inspection required
|
8/21/2026
|