MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Bottom floor hoistway door is missing a gib on the right hand side. Reinspection required.
|
11/14/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)10 Car Floors
|
|
|
Carpet inside the elevator is worn and fraying. Replace.
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Control valve in the machine room allowed oil to leak back to down side of valve during 15 minute standing test with power off. Reinspection Required.
|
11/14/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Machine room GFCI outlet not wired properly, repair.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing alarm bell to work.
|
4/23/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Reprogram emergency phone to call a 24 hour station.
|
6/11/2019
|