MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work. Dials, no answer. Attempted 3 times. Phone calls front desk, calls must be answered 24/7. Reprogram to call proper monitoring agency. 5/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Alarm bell shall work with loss of main 120v power. 5/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Car door gibs to be replaced. Gibs are cutting into car sill. 7/1/2025
MO Minimum : Elevators (I) - Pits (I)1 Clean pit 6/28/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on emergency power, annually. 5/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lighting shall work. 5/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 5/6/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove oil recovery system (scavenger Pump) from pit. 7/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair means of two way communication with car 5/7/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair pit light 7/21/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair pit lights 7/8/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light shall work. 7/1/2025