Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x x Replace all three door sills and sill support angles as the rust has built up enough to bow the sills up impeding the operation of the door , #2 will not open or close. 5/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Remove the black mold from the hoistway. The drywall is rotting away from the moisture. 4/26/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces remove the black mold from the machine room and replace the damaged dry from it. 4/26/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Adjust the machine room door as it is to be self closing and self latching. 4/26/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Replace the burnt out light tubes in the car ceiling. 8/10/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair the emergency phone as there is no dial tone 4/26/2023
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) Repair or replace the door closer to the machine room as it is to be self closing self locking at all times. 8/10/2021
A17.1-1996 : Elevators 2.4 - Machine space 1001.2(b)(4) Remove the black mold from the machine room as it is causing a health hazard. 8/10/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 8/10/2021