A17.1-1996 : Elevators
|
2.4 - Machine space
|
1001.2(b)(4)
|
|
|
Remove the black mold from the machine room as it is causing a health hazard.
|
8/10/2021
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
Repair or replace the door closer to the machine room as it is to be self closing self locking at all times.
|
8/10/2021
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Replace the burnt out light tubes in the car ceiling.
|
8/10/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a current state operating certificate in the machine room
|
8/10/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
x
|
Replace all three door sills and sill support angles as the rust has built up enough to bow the sills up impeding the operation of the door , #2 will not open or close.
|
5/19/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Adjust the machine room door as it is to be self closing and self latching.
|
4/26/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Remove the black mold from the hoistway. The drywall is rotting away from the moisture.
|
4/26/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
remove the black mold from the machine room and replace the damaged dry from it.
|
4/26/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair the emergency phone as there is no dial tone
|
4/26/2023
|