MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work. Repair phone (phone line has 54 volts in controller) Rule B-11, Missouri minimum. Rule 8.11.3.1(F) A17.2, 2014. Reinspect by 7/14/23 (30 days)
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Light shall work. Repair same.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone line does not work.
|
6/14/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work, need to repair phone line. Re-inspection required
|
9/30/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of current operating certficate needs to be properly displayed in the machine room.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current operating certificate in machine room.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency battery lowering shall work. Reinspection required within 30 days.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Make phone in car operational
|
8/3/2018
|
conversion
|
conversion
|
n/a
|
|
|
Repair emergency light in car
|
|
conversion
|
conversion
|
n/a
|
|
|
Post current State certification in machine room
|
|