Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the elevator machine room 1/17/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the elevator machine room 1/17/2025
MO Minimum : Elevators (I) - Pits (I)1 Channel drain in pit, over sump hole 2/13/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars x Debris shall be removed from the car top. The car top shall be cleaned. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Fire panel module in overhead shall be installed in the correct size box. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Heat detector in hoistway shall remove power from the elevator when activated. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 (Re-Inspection) x Heat detector in machine room shall remove power from the elevator when activated. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.39 - Low Oil Protection 3.26.9 Low Oil Protection (Re-Inspection) x Low oil protection shall be operational. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.3.1.2(c) x Machine room lights bulbs shall be guarded. 9/10/2019
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Need maintenance control program on site posted on controller 1/17/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is due for 5 year test in 2024 1/17/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) x x Phase 2 fire service shall be operational. (Could not test because door close button did not work). 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Smoke detector at 1st floor rear entry shall recall to the main landing. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Smoke detector at 2nd floor shall be operational and recall to the main landing. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Smoke detectors in machinery spaces shall recall to the main landing. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 8.11.2.1.1(c) x The door close button shall be operational. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) x The machine room shall be kept clean. Remove the debris from the machine room. 9/10/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Wireway covers and end caps shall be installed. 9/10/2019