MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the elevator machine room
|
1/17/2025
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the elevator machine room
|
1/17/2025
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Channel drain in pit, over sump hole
|
2/13/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
x
|
|
Debris shall be removed from the car top. The car top shall be cleaned.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Fire panel module in overhead shall be installed in the correct size box.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Heat detector in hoistway shall remove power from the elevator when activated.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2 (Re-Inspection)
|
x
|
|
Heat detector in machine room shall remove power from the elevator when activated.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.39 - Low Oil Protection
|
3.26.9 Low Oil Protection (Re-Inspection)
|
x
|
|
Low oil protection shall be operational.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.3.1.2(c)
|
x
|
|
Machine room lights bulbs shall be guarded.
|
9/10/2019
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Need maintenance control program on site posted on controller
|
1/17/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is due for 5 year test in 2024
|
1/17/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.1.4(l)
|
x
|
x
|
Phase 2 fire service shall be operational. (Could not test because door close button did not work).
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Smoke detector at 1st floor rear entry shall recall to the main landing.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Smoke detector at 2nd floor shall be operational and recall to the main landing.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Smoke detectors in machinery spaces shall recall to the main landing.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.3 - Operating control devices
|
8.11.2.1.1(c)
|
x
|
|
The door close button shall be operational.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(e) (Re-Inspection)
|
x
|
|
The machine room shall be kept clean. Remove the debris from the machine room.
|
9/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Wireway covers and end caps shall be installed.
|
9/10/2019
|