Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | x | OSV in the pit is not sealed and must have a category 5 test performed within 90 days or less | 11/10/2021 | |
A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | x | Remove scavenger pump from pit and replace with a 5 gallon bucket | 11/10/2021 |