Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone inoperative Repair as necessary 9/21/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Perform emergency power generator test to complete testing 9/21/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Suspension ropes are starting to rouge and are below minimum diameter replace suspension ropes. 90 days 9/21/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Perform generator testing to complete test 9/21/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone does not work, phone line has no power. Re-inspection required 8/3/2026
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Suspension ropes are starting to rouge and are below minimum diameter. Replace suspension ropes. Reinspect in 30 days 6/26/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state operating certificate in elevator machine room 6/26/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Elevator ceiling is of the egg crate type that causes no protection if the bulbs were to shatter, need to make ceiling panels solid or put plastic protection tubes around the bulbs.