Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) x x On Phase I & II fire service, elevator starts and stops and will not return to main landing. This is an entrapment hazard so elevator was taken out of service until repaired. 4/8/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed and needs to be tested on or before next annual inspection. 6/15/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x x Phase I did not initiate when the fireman's emergency service key was turned to the “ON” position. If not repaired in 15 days the elevator will be locked out of services per Gus Guadamuz. Fenton Fire Protection District has been notified along with signage posted indicating this deficiency. 4/2/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) x x Phase II did not initiate when the fireman's emergency service key was turned to the “ON” position. If not repaired in 15 days the elevator will be locked out of services per Gus Guadamuz. Fenton Fire Protection District has been notified along with signage posted indicating this deficiency. 4/2/2020
conversion conversion n/a The elevator pit has approximately 2? of water in it. The elevator pit shall be kept clean and dry. 8/27/2018