Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a All pits shall be kept dry, clean and free of equipment or material not relating to the operation of the elevator. Exception: Sump pumps. 6/28/2018
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Elevator wiring diagrams are missing from the elevatormachine room. 6/7/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Water lines (for the chiller) have been installed in the machine room, which is prohibited. 6/7/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone not programmed. 7/12/2024