Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in machine room does not have enough candle power per code. 2.3.1 1/7/2020
MO Minimum : Elevators (A) - Hoistways (A)3 Repair 1st floor door closer. 1/7/2020
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean and dry. 1/7/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated certificate in machine room. 1/7/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The Phase II Firefighters key switch shall be labeled "OFF" "HOLD" and "ON" 2/5/2024
MO Minimum : Elevators (H) - Machine Rooms (H)8 Unsecured Heat sensor hanging from ceiling exposing wiring. 2/5/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room in a frame 2/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Phase 2 key switch is not legible and does not allow the key to rotate into the correct position for phase 2 operation. 2/5/2024