MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Repair pit light
|
4/15/2019
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
2" water oil mix in pit. Remove. Pit must be clean and dry
|
2/14/2020
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit must be kept clean and dry.
|
5/6/2021
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Replace missing firefighters Phase I signage at recall floor near firefighters key switch.
|
5/6/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide MCP.
|
2/20/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean the car top.
|
2/20/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide means for two-way communication to properly function. Calls immediately drop after being answered.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Incomplete test. Fire service test shall be completed in order to complete the test. Mechanic did not have the correct key at the time of the inspection.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work properly.
|
2/20/2026
|