Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 wall between mach room and shaft where duct work penetrates needs to be sealed. 4 inch gap exists that needs cover/fire caulked 10/21/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Need Phase I Fire service instructions. Place by Fire recall switch 8/31/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working, alarm bell ok.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Provide a pit jug for each jack, in pit, not to exceed 5 gallon capacity each.