MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean and dry.
|
5/29/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Lost cab phone signal voltage. Repair.
|
5/18/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work, needs repair. Re-inspection required
|
6/8/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Place current state operating certificate in machine room
|
4/25/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
4/25/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Need to clean oil from pit floor
|
8/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Cylinder head packing is leaking oil excessively, replace same
|
8/5/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Sump pump in elevator pit is not working. Approximately 6" of standing water is in the elevator pit, need to repair sump pump
|
6/24/2025
|