Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Cab floor tile is worn, has hole. Tripping hazard, replace. 4/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, have serviced or replaced 4/5/2025
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)8 Yes Yes Overspeed governor jaw set at too high of a rate of speed, must be below 175 fpm. Red-tag & Re-inspection required 4/1/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Provide guards on bulbs to prevent accidental contact or breakage. 4/5/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Provide guards on machine room bulbs, to prevent accidental contact or breakage 4/5/2025
conversion conversion conversion - reinspect Yes No The car door restrictor device needs to be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. This will require a reinspection for compliance. 3/5/2019
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) Yes No The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. 9/11/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required. 9/11/2019
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2005. 5/11/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2005. 5/11/2020
conversion conversion n/a No No The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2005. 10/1/2018