Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/27/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. 8/27/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove all non-elevator related material from the machine room. 8/27/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 8/27/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator machine room. 10/30/2020