Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Machine room shall not be used for storage of non elevator related materials. 1/8/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The machine room shall not be used for the storage of non-elevator related items. 1/8/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/27/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 8/27/2021
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 1001.2(b)(8) Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. 8/27/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. The certificate displayed is expired.
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.