A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Machine room shall not be used for storage of non elevator related materials.
|
1/8/2019
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
The machine room shall not be used for the storage of non-elevator related items.
|
1/8/2019
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
8/27/2021
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
8/27/2021
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
1001.2(b)(8)
|
|
|
Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered.
|
8/27/2021
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. The certificate displayed is expired.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
|