Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator machine room. 1/28/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/27/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 8/27/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. The certificate displayed is expired. 11/7/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light shall be operational. 11/7/2022
MO Minimum : Elevators (A) - Hoistways (A)13 The hole in the hoistway wall in the pit where the sprinkler pipe exits shall be sealed with approved material. 11/7/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. Note: This door wasn't equipped with a closer at the time of the inspection. 12/30/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car telephone shall be operational. 11/1/2022