MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Replace the damaged door detector, it won't allow the door to close until it goes into nudging.
|
8/23/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Have the emergency phone repaired as there is no dial tone.
|
7/13/2020
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
Repair the HVAC unit in the machine room.
|
1/8/2024
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Have the fire extinguisher re-certified as yours out dated.
|
5/29/2019
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Have the fire extinguisher re-certified
|
8/19/2019
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
Replace the traveling cable that has been submerged in the water.
|
8/23/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
Remove the standing 2 feet of water in the pit.
|
8/22/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
102
|
x
|
|
Replace all the damaged electrical conduit, wiring, fixtures below the lower level floor with NEMA 4 wet location equipment.
|
8/22/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Replace the bad pit light from the high water level.
|
8/3/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
Repair or replace the smoke detector in the machine room as it will not recall the elevator as it has the wrong relay.
|
12/29/2023
|
conversion
|
conversion
|
n/a
|
|
|
Remove all stored material from the machine room as nothing can be stored in there except elevator equipment.
|
8/29/2018
|
conversion
|
conversion
|
n/a
|
|
|
Remove the standing water from the elevator pit and maintain a dry pit
|
8/29/2018
|
conversion
|
conversion
|
n/a
|
|
|
Remove all the molded & deteroated drywall and replace it back to a 2 hour rated assembly.
|
8/29/2018
|
conversion
|
conversion
|
n/a
|
|
|
Re-anchor the top of the guide rails as the wedge anchors are not there.
|
8/29/2018
|
conversion
|
conversion
|
n/a
|
|
|
Obtain and display a current state operating certificate in the machine room.
|
8/29/2018
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a current state operating certificate in the machine room
|
8/19/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a current state operating certificate in the machine room
|
8/3/2020
|