Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Obtain and display a current state operating certificate in the machine room 8/19/2019
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No Have the fire extinguisher re-certified 8/19/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Have the emergency phone repaired as there is no dial tone. 7/13/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Obtain and display a current state operating certificate in the machine room 8/3/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No Replace the bad pit light from the high water level. 8/3/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No Have the fire extinguisher re-certified as yours out dated. 5/29/2019
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No Repair the HVAC unit in the machine room. 1/8/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f Yes No Repair or replace the smoke detector in the machine room as it will not recall the elevator as it has the wrong relay. 12/29/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a Yes No Remove the standing 2 feet of water in the pit. 8/22/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 Yes No Replace all the damaged electrical conduit, wiring, fixtures below the lower level floor with NEMA 4 wet location equipment. 8/22/2024
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 No No Replace the traveling cable that has been submerged in the water. 8/23/2024
conversion conversion n/a No No Remove all stored material from the machine room as nothing can be stored in there except elevator equipment. 8/29/2018
conversion conversion n/a No No Remove the standing water from the elevator pit and maintain a dry pit 8/29/2018
conversion conversion n/a No No Remove all the molded & deteroated drywall and replace it back to a 2 hour rated assembly. 8/29/2018
conversion conversion n/a No No Re-anchor the top of the guide rails as the wedge anchors are not there. 8/29/2018
conversion conversion n/a No No Obtain and display a current state operating certificate in the machine room. 8/29/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Replace the damaged door detector, it won't allow the door to close until it goes into nudging. 8/23/2024