| conversion | conversion | n/a |  |  | Remove all stored material from the machine room as nothing can be stored in there except elevator equipment. | 8/29/2018 | 
                
                    | conversion | conversion | n/a |  |  | Remove the standing water from the elevator pit and maintain a dry pit | 8/29/2018 | 
                
                    | conversion | conversion | n/a |  |  | Remove all the molded & deteroated drywall and replace it back to a 2 hour rated assembly. | 8/29/2018 | 
                
                    | conversion | conversion | n/a |  |  | Re-anchor the top of the guide rails as the wedge anchors are not there. | 8/29/2018 | 
                
                    | conversion | conversion | n/a |  |  | Obtain and display a current state operating certificate in the machine room. | 8/29/2018 | 
                
                    | A17.1-1996 : Elevators | CSR  40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | Obtain and display a current state operating certificate in the machine room | 8/19/2019 | 
                
                    | A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) |  |  | Have the fire extinguisher re-certified | 8/19/2019 | 
                
                    | A17.1-1996 : Elevators | CSR  40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | Obtain and display a current state operating certificate in the machine room | 8/3/2020 | 
                
                    | A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 |  |  | Replace the bad pit light from the high water level. | 8/3/2020 | 
                
                    | A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h |  |  | Have the fire extinguisher re-certified as yours out dated. | 5/29/2019 | 
                
                    | A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b |  |  | Repair the HVAC unit in the machine room. | 1/8/2024 | 
                
                    | A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 |  |  | Replace the traveling cable that has been submerged in the water. | 8/23/2024 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems |  |  | Replace the damaged door detector, it won't allow the door to close until it goes into nudging. | 8/23/2024 | 
                
                    | A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x |  | Repair or replace the smoke detector in the machine room as it will not recall the elevator as it has the wrong relay. | 12/29/2023 | 
                
                    | A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | x |  | Remove the standing 2 feet of water in the pit. | 8/22/2024 | 
                
                    | A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | x |  | Replace all the damaged electrical conduit, wiring, fixtures below the lower level floor with NEMA 4 wet location equipment. | 8/22/2024 | 
                
                    | A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x |  | Have the emergency phone repaired as there is no dial tone. | 7/13/2020 |