Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Remove all stored material from the machine room as nothing can be stored in there except elevator equipment. 8/29/2018
conversion conversion n/a Remove the standing water from the elevator pit and maintain a dry pit 8/29/2018
conversion conversion n/a Remove all the molded & deteroated drywall and replace it back to a 2 hour rated assembly. 8/29/2018
conversion conversion n/a Re-anchor the top of the guide rails as the wedge anchors are not there. 8/29/2018
conversion conversion n/a Obtain and display a current state operating certificate in the machine room. 8/29/2018
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 8/19/2019
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Have the fire extinguisher re-certified 8/19/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 8/3/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Replace the bad pit light from the high water level. 8/3/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Have the fire extinguisher re-certified as yours out dated. 5/29/2019
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b Repair the HVAC unit in the machine room. 1/8/2024
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 Replace the traveling cable that has been submerged in the water. 8/23/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Replace the damaged door detector, it won't allow the door to close until it goes into nudging. 8/23/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Repair or replace the smoke detector in the machine room as it will not recall the elevator as it has the wrong relay. 12/29/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Remove the standing 2 feet of water in the pit. 8/22/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 x Replace all the damaged electrical conduit, wiring, fixtures below the lower level floor with NEMA 4 wet location equipment. 8/22/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Have the emergency phone repaired as there is no dial tone. 7/13/2020