Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.12 - Car enclosure 204 Tighten car hand rail as needed.
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) x Provide existing battery backup lowering unit to work properly.
A17.1-1996 : Elevators 1.19 - Car Ride 203.2 Excessive noise in the down direction, repair as needed.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Provide existing emergency lights and bell to work properly.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Replace emergency light battery. 5/10/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unable to access the machine room. 4/17/2024
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection Provide means to collect oil from the piston (L) in the pit. Remove oil line returning to the tank.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.