Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Phase I operating instructions shall be posted at key switch 4/2/2022
A17.1-1996 : Elevators 3.23 - Suspension rope 212 x Properly tension suspension ropes. Re-inspection required 2/3/2023
A17.1-1996 : Elevators 3.33 - Compensating ropes and chains 202.4 x Compensation chain needs shortened. Re-inspection required 2/3/2023
A17.1-2016 : Elevators 3.33 - Compensating ropes and chains 8.6.4.1 Compensation ropes are rubbing the pit floor and need to be shortened. 3/6/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Install phase I fire service operating instructions at phase I key switch. 3/6/2023