Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.20 - Governor rope 206.5 Yes Yes Governor rope is rusted and needs to be replaced. Red-tagged, removed form service. Re-inspection required
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 Yes Yes Spring buffer stands are rusted and need to be replaced. Red-tagged, removed from service. Re-inspection required
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Machine room is not to be used as a storage closet.
A17.1-1996 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 1206.2(c) No No Provide standard railing on the car top that meets the code
A17.1-1996 : Elevators 1.6 - Car emergency signal 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair inoperative emergency phone. 8/27/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency light, bell and phone do not work on 110v emergency power. Reinspect in 14 days. 4/5/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Existing phone not working. 4/5/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Phone was not working at time of inspection. 7/7/2022