Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x This test is incomplete. The control system computer failed to boot up after the 15 minute leak down test. All the following uncompleted inspection items must be tested and witnessed: run the hoistway, check the pit and all devices in the pit, test fire service phase 1 & 2, test the door torque. 10/24/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide current tested 7/21/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 11/7/2023