ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
8/4/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Tested elevator on simulated emergency power. There are some problems in the transfer switch. Proper emergency power operation shall be tested once corrections are made.
|
5/4/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection)
|
x
|
|
The hoist ropes have reached the minimum acceptable diameter and shall be replaced and re-inspected within 90 days.
|
9/22/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.11.2.1.5(b)
|
x
|
|
The counterweight runby is too short. Provide code compliant counterweight runby.
|
5/8/2023
|