Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/4/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Tested elevator on simulated emergency power. There are some problems in the transfer switch. Proper emergency power operation shall be tested once corrections are made. 5/4/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) x The counterweight runby is too short. Provide code compliant counterweight runby. 5/8/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) x The hoist ropes have reached the minimum acceptable diameter and shall be replaced and re-inspected within 90 days. 9/22/2020