Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.40 - Maintenance Records 210.1d Inspection Operation. Provide maintenance records
conversion conversion n/a Remove all non-elevator related items from elevator machine room.
conversion conversion n/a Display of State Operating Certificate. The owner, operator, lessee or agent of either shall post the operating certificate in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. For installations without an elevator room the state-operating certificate shall be posted as directed by the chief elevator inspector.
conversion conversion n/a All elevator machine rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without use of a key.
conversion conversion n/a The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel
MO Minimum : Elevators (H) - Machine Rooms (H)2 Remove all non-elevator related items from elevator machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)2 All elevator machine rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without use of a key
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display of State Operating Certificate. The owner, operator, lessee or agent of either shall post the operating certificate in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. For installations without an elevator room the state-operating certificate shall be posted as directed by the chief elevator inspector.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Provide fire service keys. none were on sight during the annual test. A reinspection is required to complete the annual inspection of the fire service.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Provide monthly fire service test log