Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Shorten ropes, no runby present. 2/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Provide maintenance on all landing door assemblies, rollers, upthrust, etc. All comonents in need of maintenance. 2/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean car top.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Provide MCP in machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Provide monthly FFS testing log in machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Provide MCP in machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)4 Clean machine room.
MO Minimum : Elevators (I) - Pits (I)1 Clean pit.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Replace worn hoisting ropes. 1/23/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x Emergency power not tested at time of inspection. 1/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 x Emergency power not tested at time of inspection. 2/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.27 - Rope fastenings 8.11.2.1.2(y) Counterweight shackles missing anti spin device.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room.