Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test and log firefighter operation monthly 11/17/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(4) Post emergency evacuation of passengers procedure inside machine room 11/17/2020
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Keyswitches on car control station need to have identification markings. 11/17/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test operation of elevator on emergency power with inspector present. 12/8/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test operation of elevator on emergency power 11/9/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) MRL not up to date 12/7/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test emergency power operation 12/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 12/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2.3 (Elevator Emergency Power Illuminated Signal) (Re-Inspection) x Install illuminated signal marked "Elevator Emergency Power " in the lobby at the designated landing 6/1/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide illuminated signal marked "Elevator Emergency Power " in the lobby at designated level. 10/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2.3 (Elevator Emergency Power Illuminated Signal) (Re-Inspection) x Install illuminated signal marked "Elevator Emergency Power " in the lobby at designated landing 11/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Pit light does not illuminate. 7/31/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys (Re-Inspection) x Install FEO-K1 keyswitches. All elevators in the same building shall have firefighter keyswitches operable by the same key. 12/8/2021
conversion conversion n/a Need to post fire service instructions next to Phase 1 fire service keyswitch 7/31/2018