conversion
|
conversion
|
n/a
|
|
|
Need to post fire service instructions next to Phase 1 fire service keyswitch
|
7/31/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Pit light does not illuminate.
|
7/31/2018
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Test and log firefighter operation monthly
|
11/17/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(b)(4)
|
|
|
Post emergency evacuation of passengers procedure inside machine room
|
11/17/2020
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
Keyswitches on car control station need to have identification markings.
|
11/17/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
MRL not up to date
|
12/7/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
12/14/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal) (Re-Inspection)
|
x
|
|
Install illuminated signal marked "Elevator Emergency Power " in the lobby at the designated landing
|
6/1/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test emergency power operation
|
12/13/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
|
Install FEO-K1 keyswitches. All elevators in the same building shall have firefighter keyswitches operable by the same key.
|
12/8/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test operation of elevator on emergency power with inspector present.
|
12/8/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide illuminated signal marked "Elevator Emergency Power " in the lobby at designated level.
|
10/25/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal) (Re-Inspection)
|
x
|
|
Install illuminated signal marked "Elevator Emergency Power " in the lobby at designated landing
|
11/9/2022
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test operation of elevator on emergency power
|
11/9/2022
|