Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No a monthly fire service test log is to be kept in the machine room 3/15/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No a new copy of the state operating certificate is to be posted in the machine room every year 3/15/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) No No A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. 3/15/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No pit ladder or handgrips shall extend not less than 48inches above the sill of the access door 3/15/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current copy of the State Operating Certificate in the machine room 3/15/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Post instructions for viewing on-site the records for the Maintenance Control Program (MCP) 3/15/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Post monthly fire service test log in the machine room 3/15/2026
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 3/15/2026