ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Clean up rusted pit equipment and prevent accumulation of groundwater in the pit (2.2.2.3)
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
|
|
did not have a monthly fire service test log in the machine room
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
did not have a written record of the maintenance performed on the elevator in the machine room
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Door restrictor needs to be adjusted so that the restrictor works
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
emergency lights did not come on, repair the emergency light system
|
5/30/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone continues to ring even after answering service answers the phone, the ringing makes two way conversation next to impossible
|
11/14/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, would not connect to answering service
|
6/25/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
need to have Maintenance Control Program (MCP) book in the machine room
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency lights did not come on, the alarm bell worked, replace the batteries, verify the battery charger is functioning.
|
6/3/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(c)
|
|
|
The Maintenance Control Program On-Site documents are not in the machine room.
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the machine room is to be updated annually, the certificate in the machine room is from 2016
|
|