MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
10/22/2023
|
A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
1001.2(a)(12)
|
|
|
The handrail on the back of the cab is loose.
|
12/10/2021
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
In cab emergency lighting shall work.
|
4/29/2021
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
The in car emergency lighting shall be operational.
|
4/29/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work with 24/7 support.
|
6/21/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Could not complete inspection due to difficulty getting unintended motion parameter to hold status. The following items still need be tested: (1) Testing of emergency light, alarm and/or bell with 110V source removed, (2) run and scan of the hoistway, (3) fire service testing, (4) complete category 5 test.
|
10/19/2022
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
The machine room shall not be used for storage of non-elevator related items.
|
4/29/2021
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
The lighting at the top of the hoistway for the machinery space does not work. Take corrective action.
|
10/22/2023
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP shall be provided. Currently missing evacuation plan, fire service testing log, maintenance log, and repair log.
|
12/10/2021
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
x
|
|
Provide existing pit light to work.
|
6/21/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Clean the pit of dirt and debris.
|
10/22/2023
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
All phases of fire service shall be tested.
|
7/10/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Counterweight buffer shall be tested.
|
7/10/2018
|