Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x All phases of fire service shall be tested. 7/10/2018
conversion conversion conversion - reinspect x Counterweight buffer shall be tested. 7/10/2018
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits x Provide existing pit light to work. 6/21/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide existing phone to work with 24/7 support. 6/21/2019
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 In cab emergency lighting shall work. 4/29/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The machine room shall not be used for storage of non-elevator related items. 4/29/2021
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 The in car emergency lighting shall be operational. 4/29/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP shall be provided. Currently missing evacuation plan, fire service testing log, maintenance log, and repair log. 12/10/2021
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) The handrail on the back of the cab is loose. 12/10/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Could not complete inspection due to difficulty getting unintended motion parameter to hold status. The following items still need be tested: (1) Testing of emergency light, alarm and/or bell with 110V source removed, (2) run and scan of the hoistway, (3) fire service testing, (4) complete category 5 test. 10/19/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Clean the pit of dirt and debris. 10/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 10/22/2023
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting The lighting at the top of the hoistway for the machinery space does not work. Take corrective action. 10/22/2023