MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
5/8/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022)
|
8/1/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
There is no state operating certificate in the machine room.
|
10/12/2023
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Room and Machinery Space
|
|
|
Non-elevator related items shall not be stored in the machine room. (HVAC materials, refrigerant, etc.)
|
12/5/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
|
|
Machine room lighting shall be repaired. One or more bulbs are not working.
|
12/5/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Fire service testing must be properly documented.
|
12/5/2024
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.7.2 Seizing of Rope Ends
|
|
|
Suspension rope tail ends shall be properly seized/banded. Electrical tape is not proper.
|
12/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Counterweight runby signage needs to be updated with proper maximum allowable measurement. Currently states 22", at which the overhead deflector sheave would crush cartop handrail.
|
12/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
2.4.7.2 - Cartop refuge space needs to be properly marked to allow for 43" of refuge after counterweight full compression and car bounce calculations.
|
12/5/2024
|