Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher out of date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Hoistway swing door to sill clearance over 3/4 inch. 2016 5.3.1.7.2 7/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Hoistway door to sill clearance over 3/4 in. Homemade baffles too far from floor also.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door must be self-closing and self-locking
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door must be self-closing and self-locking
MO Minimum : Elevators (I) - Pits (I)7 No No Stop switch needed in pit
MO Minimum : Elevators (I) - Pits (I)7 No No Stop switch needed in pit
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) No Yes Main hoist ropes showing signs of internal breakage. Unit removed from service. 10/26/2018
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes Yes Incorrect type and size of new ropes. Red tag remains in effect. 4/18/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(a) Elevators Placed in Inactive Status Yes Yes Elevator being placed on Inactive Status for 2 years. Will allow time for Out of Service requirements if decided on. All fuses removed. Wiring disconnected at circuit breaker. All doors closed and locked.