Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to test elevator for operation on emergency power. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to test elevator for operation on emergency power. Re-inspection required 3/25/2026
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Need to test phase I & II fire service. Re-inspection required 3/25/2026
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Phase I fire service operating instructions are missing at the phase I fire service key switch. Need to install correct signage 3/25/2026
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Phase I fire service operating instructions are missing at the phase I fire service key switch. Need to install correct signage 5/11/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean oil & debris from elevator car top
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Repair machine room air conditioner, will not turn on
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency light does not work. 9/3/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. 3/25/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No No ventilation in machine room. Controllers under extreme heat, more than manufacturers recommendations. 101.5b 3/25/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Elevator car door restrictor does not work, needs repaired. Re-inspection required 3/25/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Elevator car door restrictor does not work, needs repaired. Re-inspection required 5/11/2026