Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Cab flooring is loose, protruding above car sill causing trip hazard. 10/13/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Repair cab floor at opening, it is a tripping hazard 10/13/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No ventilation in machine room. Controllers are in extreme heat, over manufacturers recommendations. 101.5b 10/13/2022
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)7 x x The elevator safety governor was found to be worn to a degree that the activation would not set with any sort of consistency. Repair or replacement of the governor is required and a re-inspection shall be performed before the elevator can be returned to service. 11/8/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated Missouri Operating Certificate in machine room